Template · Solar and storage

Grid-tied PV, string inverter single line diagram

Load-side connection through a 40A backfed breaker. Use this for a typical residential rooftop system with one string inverter, connected through a backfed breaker in the main panel. It suits a panel whose bus has room for the solar breaker under the busbar check.

A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.

Open this template in the editor Download the SVG

Grid-tied PV, string inverter single line diagram: load-side connection through a 40A backfed breaker.
Grid-tied PV, string inverter. 11 devices on an 11 × 17 in sheet with a title block and notes column.

What the reviewer checks on this drawing

The reviewer checks the busbar arithmetic, the PV breaker at the opposite end of the bus from the main, the inverter output at 125%, the AC disconnect and rapid shutdown.

What the drawing shows

Every device on the sheet, in the order power reaches it.

SymbolLabelRating or detailConductors feeding it
Utility sourceUtility service120/240V 1φ 3W
MeterUtility meter200A socketService conductors, per utility
Circuit breaker200A 2PMain breaker
PanelMain panel200A bus · 120/240V
Circuit breakerExistingBranch breakers
LoadExisting loads
Circuit breaker40A 2PPV backfeed, opposite end from main
Disconnect switchAC disconnect60A non-fused, lockable, visible blade3 #8 Cu + #10 G
InverterString inverter7.6 kW · 240V · 32A, integrated DC disconnect
DeviceRapid shutdown (RSD)Module-level devicesPV wire #10 Cu, 2 strings
PV arrayPV array20 × 400W = 8.0 kW DC

Notes on the sheet

  • Busbar check: 200A bus × 120% = 240A ≥ 200A main + 40A PV breaker (NEC 705.12).
  • PV breaker located at the opposite end of the bus from the main breaker and labelled.
  • Inverter output 32A × 125% = 40A.
  • Rapid shutdown per NEC 690.12 (CEC Rule 64-218).

Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.

See all solar and battery single line diagrams, or all 40 templates.

Start from this drawing