PV supply-side connection single line diagram
Line-side tap with a fused, service-rated PV disconnect. Use this when the panel bus cannot take a backfed breaker. The PV connects on the line side of the main breaker instead, through its own fused disconnect.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks that the utility and the AHJ accept a supply-side connection, that the PV disconnect is service rated with the neutral bonded in it, and the fuse size against 125% of the inverter output.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Device | Supply-side connection (TAP) | Listed connectors in rated enclosure | |
| Circuit breaker | 200A 2P | Existing main | |
| Panelboard | Main panel | Existing 200A | |
| Fused disconnect | PV disconnect | 60A fused · 50A fuses, service rated | |
| Inverter | String inverter | 9.6 kW · 240V · 40A | 3 #6 Cu + #6 G |
| PV array | PV array | 26 × 400W = 10.4 kW DC | PV wire #10 Cu, 3 strings |
Notes on the sheet
- Supply-side connection per NEC 705.11. The PV disconnect is service equipment: neutral bonded to the enclosure.
- Inverter output 40A × 125% = 50A fuses.
- Confirm the utility and AHJ accept a supply-side connection before design.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related solar and battery drawings
Grid-tied PV, string inverter
Load-side connection through a 40A backfed breaker.
Solar · storageView drawingGrid-tied PV, microinverters
Two microinverter branches combined in an AC combiner.
Solar · storageView drawingPV and storage, hybrid inverter
DC-coupled battery with a backup loads panel.
Solar · storageView drawingBattery with partial home backup
Backup gateway and a dedicated backup loads panel.
Solar · storageView drawingSee all solar and battery single line diagrams, or all 40 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.