Standby generator, whole-home ATS single line diagram
Service-rated 200A automatic transfer switch. Use this for a permanently installed standby generator that backs up the whole house through a service-rated 200A automatic transfer switch.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks the transfer switch as the new service disconnect, with the grounding electrode conductor and main bonding jumper landing there; the old main panel converted to a subpanel; the generator breaker; and load shedding if the calculated load is more than the generator can carry.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Transfer switch | Automatic transfer switch | 200A · service rated, main disconnect inside | |
| Circuit breaker | 100A 2P | Generator breaker | |
| Generator | Standby generator | 22 kW · 120/240V, natural gas | |
| Panel | Main panel | 200A bus · neutrals isolated | 3 #3/0 Cu + #6 G |
| Circuit breaker | Existing | All house loads | |
| Load | Existing loads |
Notes on the sheet
- Transfer switch is the service disconnect. Grounding electrode conductor and main bonding jumper terminate at the transfer switch.
- Existing main panel becomes a subpanel: isolate neutrals and remove the bonding screw.
- Generator 22 kW ÷ 240V = 92A, protected at 100A.
- Load shedding modules added if the calculated load exceeds the generator rating.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related generator drawings
Portable generator inlet with interlock
Backfed 30A breaker mechanically interlocked with the main.
GeneratorView drawingGenerator with manual transfer switch
Ten-circuit manual transfer switch with an inlet box.
GeneratorView drawingStandby generator, essential loads panel
100A transfer switch feeding an essential loads subpanel.
GeneratorView drawing400A service with ATS and 200A generator
Service-rated 400A transfer switch feeding two 200A panels.
GeneratorView drawingSee all generator single line diagrams, or all 40 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.