Level 2 charger from main panel single line diagram
Dedicated 60A circuit to a hardwired 48A charger. Use this for the simplest Level 2 install: one hardwired charger on its own breaker in a main panel that has the capacity for it. If the load calculation does not leave room for 48A of continuous load, start from the load-management drawing instead.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks the 60A breaker against the 48A charger (125%), the branch conductor size, and that a service load calculation supports the added load.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Circuit breaker | 200A 2P | Main breaker | |
| Panel | Main panel | 200A bus · 120/240V | |
| Ground | Grounding electrode system | ||
| Circuit breaker | Existing | Branch breakers | |
| Load | Existing loads | ||
| Circuit breaker | 60A 2P | New | |
| EV charger | Level 2 EVSE | 48A continuous, 11.5 kW · hardwired | 2 #6 Cu THHN + #10 G, 3/4" EMT |
Notes on the sheet
- EVSE is a continuous load: 48A × 125% = 60A branch circuit.
- Service load calculation to confirm capacity for the added EVSE load.
- EVSE to be listed and installed per manufacturer instructions.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related EV charger drawings
Level 2 charger with load management
Energy management system sheds the charger when the service is near its limit.
EVView drawingCharger from subpanel with load management
Garage subpanel feeds the charger through an energy management system.
EVView drawingCondo charger from meter with load miser
Load management device between the unit meter and unit panel feeds the charger.
EVView drawingTwo chargers with power sharing
A 100A EV load centre feeds two chargers that share a group current limit.
EVView drawingSee all EV charger single line diagrams, or all 40 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.