480Y/277V service with 208V transformer single line diagram
800A switchboard with a 75 kVA transformer for 120/208V loads. Use this for a commercial service at 480Y/277V: an 800A switchboard with a 75 kVA transformer for the 120/208V loads.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks the transformer and the bonding of its secondary, arc-flash and available fault current labels on the switchboard, and, where required, selective coordination reviewed by the engineer of record.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail |
|---|---|---|
| Utility source | Utility transformer | 480Y/277V 3φ 4W |
| Current transformer | CT cabinet | Utility metering |
| Circuit breaker | 800A 3P | Main |
| Panel | Main switchboard MSB | 800A · 480Y/277V 3φ 4W |
| Circuit breaker | 225A 3P | HP-1 |
| Panelboard | Panel HP-1 | 277V lighting, HVAC |
| Circuit breaker | 125A 3P | T-1 primary |
| Transformer | Transformer T-1 | 75 kVA, 480V Δ – 208Y/120V |
| Circuit breaker | 225A 3P | Secondary main |
| Panelboard | Panel LP-1 | 225A · 208Y/120V |
| Circuit breaker | 100A 3P | RTU-1 |
| Disconnect switch | Disconnect | 100A · NEMA 3R |
| Load | RTU-1 | Rooftop unit |
| Circuit breaker | 30A 3P | SPD |
| Device | Surge protective device (SPD) |
Notes on the sheet
- Transformer T-1: 90A primary, 208A secondary. Secondary bonded as a separately derived system.
- Arc-flash and available fault current labels applied to the switchboard.
- Selective coordination and arc energy reduction reviewed by the engineer of record where required.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related commercial and industrial drawings
347/600V service with step-down transformer
Canadian commercial service with a 75 kVA transformer to 120/208V.
CommercialView drawingTenant fit-up panel
New metered 100A feeder and panel from base-building distribution.
CommercialView drawingMotor control centre
MCC with starters, a drive, a lighting transformer and a spare bucket.
CommercialView drawingMotor branch circuit with VFD
Drive, shielded cable and a motor disconnect within sight.
CommercialView drawingSee all commercial and industrial single line diagrams, or all 40 templates.