Template · Commercial and industrial

480Y/277V service with 208V transformer single line diagram

800A switchboard with a 75 kVA transformer for 120/208V loads. Use this for a commercial service at 480Y/277V: an 800A switchboard with a 75 kVA transformer for the 120/208V loads.

A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.

Open this template in the editor Download the SVG

480Y/277V service with 208V transformer single line diagram: 800A switchboard with a 75 kVA transformer for 120/208V loads.
480Y/277V service with 208V transformer. 15 devices on an 11 × 17 in sheet with a title block and notes column.

What the reviewer checks on this drawing

The reviewer checks the transformer and the bonding of its secondary, arc-flash and available fault current labels on the switchboard, and, where required, selective coordination reviewed by the engineer of record.

What the drawing shows

Every device on the sheet, in the order power reaches it.

SymbolLabelRating or detail
Utility sourceUtility transformer480Y/277V 3φ 4W
Current transformerCT cabinetUtility metering
Circuit breaker800A 3PMain
PanelMain switchboard MSB800A · 480Y/277V 3φ 4W
Circuit breaker225A 3PHP-1
PanelboardPanel HP-1277V lighting, HVAC
Circuit breaker125A 3PT-1 primary
TransformerTransformer T-175 kVA, 480V Δ – 208Y/120V
Circuit breaker225A 3PSecondary main
PanelboardPanel LP-1225A · 208Y/120V
Circuit breaker100A 3PRTU-1
Disconnect switchDisconnect100A · NEMA 3R
LoadRTU-1Rooftop unit
Circuit breaker30A 3PSPD
DeviceSurge protective device (SPD)

Notes on the sheet

  • Transformer T-1: 90A primary, 208A secondary. Secondary bonded as a separately derived system.
  • Arc-flash and available fault current labels applied to the switchboard.
  • Selective coordination and arc energy reduction reviewed by the engineer of record where required.

Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.

See all commercial and industrial single line diagrams, or all 40 templates.

Start from this drawing

Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.