347/600V service with step-down transformer single line diagram
Canadian commercial service with a 75 kVA transformer to 120/208V. Use this for a Canadian commercial service at 347/600V, with a 75 kVA step-down transformer for the 120/208V loads.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks the transformer’s primary and secondary currents and protection, the bonding of the secondary as a separately derived system, and equipment short-circuit ratings against the fault current stated by the utility.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 347/600V 3φ 4W | |
| Current transformer | CT cabinet | Utility metering | |
| Fused disconnect | Main switch | 400A · 600V, fused 400A | |
| Panel | Distribution panel CDP | 400A · 347/600V 3φ 4W | |
| Circuit breaker | 100A 3P | LP-1 | |
| Panelboard | Panel LP-1 | 347V lighting | |
| Circuit breaker | 100A 3P | T-1 primary | |
| Transformer | Transformer T-1 | 75 kVA, 600V Δ – 120/208V Y | 3 #3 Cu + #8 G |
| Circuit breaker | 225A 3P | Secondary main | |
| Panelboard | Panel PP-1 | 225A · 120/208V | |
| Circuit breaker | 60A 3P | RTU-1 | |
| Disconnect switch | Disconnect | 60A · NEMA 3R | |
| Load | RTU-1 | Rooftop unit | |
| Circuit breaker | 30A 3P | SPD | |
| Device | Surge protective device (SPD) |
Notes on the sheet
- Transformer T-1: 72A primary, 208A secondary. Secondary neutral bonded and grounded as a separately derived system.
- Equipment short-circuit ratings to equal or exceed the available fault current stated by the utility.
- Identify each panel and disconnect with a permanent engraved nameplate.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related commercial and industrial drawings
480Y/277V service with 208V transformer
800A switchboard with a 75 kVA transformer for 120/208V loads.
CommercialView drawingTenant fit-up panel
New metered 100A feeder and panel from base-building distribution.
CommercialView drawingMotor control centre
MCC with starters, a drive, a lighting transformer and a spare bucket.
CommercialView drawingMotor branch circuit with VFD
Drive, shielded cable and a motor disconnect within sight.
CommercialView drawingSee all commercial and industrial single line diagrams, or all 40 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.