Template · Commercial and industrial

347/600V service with step-down transformer single line diagram

Canadian commercial service with a 75 kVA transformer to 120/208V. Use this for a Canadian commercial service at 347/600V, with a 75 kVA step-down transformer for the 120/208V loads.

A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.

Open this template in the editor Download the SVG

347/600V service with step-down transformer single line diagram: canadian commercial service with a 75 kVA transformer to 120/208V.
347/600V service with step-down transformer. 15 devices on an 11 × 17 in sheet with a title block and notes column.

What the reviewer checks on this drawing

The reviewer checks the transformer’s primary and secondary currents and protection, the bonding of the secondary as a separately derived system, and equipment short-circuit ratings against the fault current stated by the utility.

What the drawing shows

Every device on the sheet, in the order power reaches it.

SymbolLabelRating or detailConductors feeding it
Utility sourceUtility service347/600V 3φ 4W
Current transformerCT cabinetUtility metering
Fused disconnectMain switch400A · 600V, fused 400A
PanelDistribution panel CDP400A · 347/600V 3φ 4W
Circuit breaker100A 3PLP-1
PanelboardPanel LP-1347V lighting
Circuit breaker100A 3PT-1 primary
TransformerTransformer T-175 kVA, 600V Δ – 120/208V Y3 #3 Cu + #8 G
Circuit breaker225A 3PSecondary main
PanelboardPanel PP-1225A · 120/208V
Circuit breaker60A 3PRTU-1
Disconnect switchDisconnect60A · NEMA 3R
LoadRTU-1Rooftop unit
Circuit breaker30A 3PSPD
DeviceSurge protective device (SPD)

Notes on the sheet

  • Transformer T-1: 72A primary, 208A secondary. Secondary neutral bonded and grounded as a separately derived system.
  • Equipment short-circuit ratings to equal or exceed the available fault current stated by the utility.
  • Identify each panel and disconnect with a permanent engraved nameplate.

Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.

See all commercial and industrial single line diagrams, or all 40 templates.