Charger from subpanel with load management single line diagram
Garage subpanel feeds the charger through an energy management system. Use this when the charger is fed from a garage subpanel instead of the main panel, and the subpanel feeder is the limit. The EVEMS watches the feeder, not the service.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer looks for the feeder rating, the point where its current is measured, and a subpanel with isolated neutrals and bonded equipment grounds.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Circuit breaker | 200A 2P | Main breaker | |
| Panel | Main panel | 200A bus · 120/240V | |
| Circuit breaker | Existing | Branch breakers | |
| Load | Existing loads | ||
| Circuit breaker | 100A 2P | Feeder | |
| Panel | Garage subpanel | 100A MLO · 120/240V | 3 #3 Cu + #8 G |
| Circuit breaker | Existing | Garage circuits | |
| Load | Existing loads | ||
| Circuit breaker | 60A 2P | New | |
| Device | Energy management system (EVEMS) | CTs on subpanel feeder | |
| EV charger | Level 2 EVSE | 48A · 11.5 kW |
Notes on the sheet
- EVEMS monitors the subpanel feeder and interrupts the EVSE before the feeder rating is exceeded.
- Subpanel neutrals isolated from the enclosure; equipment grounds bonded.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related EV charger drawings
Level 2 charger from main panel
Dedicated 60A circuit to a hardwired 48A charger.
EVView drawingLevel 2 charger with load management
Energy management system sheds the charger when the service is near its limit.
EVView drawingCondo charger from meter with load miser
Load management device between the unit meter and unit panel feeds the charger.
EVView drawingTwo chargers with power sharing
A 100A EV load centre feeds two chargers that share a group current limit.
EVView drawingSee all EV charger single line diagrams, or all 40 templates.