PV and storage, hybrid inverter single line diagram
DC-coupled battery with a backup loads panel. Use this for solar with a DC-coupled battery on a hybrid inverter that keeps a backup loads panel running in an outage.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks the busbar arithmetic with the main breaker derated to 175A, the inverter’s grid connection at 125%, and that the backup panel is isolated from the grid while the inverter is islanded.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Circuit breaker | 175A 2P | Main breaker, derated from 200A | |
| Panel | Main panel | 200A bus · 120/240V | |
| Circuit breaker | Existing | Branch breakers | |
| Load | Existing loads | ||
| Circuit breaker | 60A 2P | Hybrid inverter | |
| Inverter | Hybrid inverter | 11.4 kW · 48A grid port | 3 #6 Cu + #10 G |
| Battery | Battery | 10 kWh · LFP | |
| PV array | PV array | DC-coupled · 10 kW DC | |
| Panel | Backup loads panel | 100A MLO · 120/240V | 3 #6 Cu + #10 G |
| Circuit breaker | Branch | Backed-up circuits | |
| Load | Critical loads |
Notes on the sheet
- Busbar check: 200A bus × 120% = 240A ≥ 175A main + 60A inverter breaker. Main breaker replaced with 175A; inverter breaker at the opposite end of the bus.
- Inverter grid port 48A × 125% = 60A.
- Backup loads panel is isolated from the grid by the inverter during an outage.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related solar and battery drawings
Grid-tied PV, string inverter
Load-side connection through a 40A backfed breaker.
Solar · storageView drawingGrid-tied PV, microinverters
Two microinverter branches combined in an AC combiner.
Solar · storageView drawingPV supply-side connection
Line-side tap with a fused, service-rated PV disconnect.
Solar · storageView drawingBattery with partial home backup
Backup gateway and a dedicated backup loads panel.
Solar · storageView drawingSee all solar and battery single line diagrams, or all 40 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.