Template · Solar and storage

Grid-tied PV, microinverters single line diagram

Two microinverter branches combined in an AC combiner. Use this for a rooftop system with a microinverter under each module. The circuits are AC from the roof down, joined in an AC combiner and landed on one breaker in the main panel.

A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.

Open this template in the editor Download the SVG

Grid-tied PV, microinverters single line diagram: two microinverter branches combined in an AC combiner.
Grid-tied PV, microinverters. 13 devices on an 11 × 17 in sheet with a title block and notes column.

What the reviewer checks on this drawing

The reviewer checks the number of microinverters and their combined current at 125%, the combiner, the busbar arithmetic, and that the microinverters provide module-level rapid shutdown.

What the drawing shows

Every device on the sheet, in the order power reaches it.

SymbolLabelRating or detailConductors feeding it
Utility sourceUtility service120/240V 1φ 3W
MeterUtility meter200A socketService conductors, per utility
Circuit breaker200A 2PMain breaker
PanelMain panel200A bus · 120/240V
Circuit breakerExistingBranch breakers
LoadExisting loads
Circuit breaker30A 2PPV backfeed
Disconnect switchAC disconnect30A non-fused, lockable3 #10 Cu + #10 G
PanelAC combiner60A · 240V
Circuit breaker20A 2PBranch 1
PV arrayPV branch 19 modules with microinverters
Circuit breaker20A 2PBranch 2
PV arrayPV branch 29 modules with microinverters

Notes on the sheet

  • 18 microinverters × 1.21A = 21.8A; × 125% = 27.2A, protected at 30A.
  • Busbar check: 200A bus × 120% = 240A ≥ 200A main + 30A PV breaker. PV breaker at the opposite end of the bus from the main.
  • Microinverters provide module-level rapid shutdown.

Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.

See all solar and battery single line diagrams, or all 40 templates.

Start from this drawing

Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.