Grid-tied PV, microinverters single line diagram
Two microinverter branches combined in an AC combiner. Use this for a rooftop system with a microinverter under each module. The circuits are AC from the roof down, joined in an AC combiner and landed on one breaker in the main panel.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks the number of microinverters and their combined current at 125%, the combiner, the busbar arithmetic, and that the microinverters provide module-level rapid shutdown.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Circuit breaker | 200A 2P | Main breaker | |
| Panel | Main panel | 200A bus · 120/240V | |
| Circuit breaker | Existing | Branch breakers | |
| Load | Existing loads | ||
| Circuit breaker | 30A 2P | PV backfeed | |
| Disconnect switch | AC disconnect | 30A non-fused, lockable | 3 #10 Cu + #10 G |
| Panel | AC combiner | 60A · 240V | |
| Circuit breaker | 20A 2P | Branch 1 | |
| PV array | PV branch 1 | 9 modules with microinverters | |
| Circuit breaker | 20A 2P | Branch 2 | |
| PV array | PV branch 2 | 9 modules with microinverters |
Notes on the sheet
- 18 microinverters × 1.21A = 21.8A; × 125% = 27.2A, protected at 30A.
- Busbar check: 200A bus × 120% = 240A ≥ 200A main + 30A PV breaker. PV breaker at the opposite end of the bus from the main.
- Microinverters provide module-level rapid shutdown.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related solar and battery drawings
Grid-tied PV, string inverter
Load-side connection through a 40A backfed breaker.
Solar · storageView drawingPV supply-side connection
Line-side tap with a fused, service-rated PV disconnect.
Solar · storageView drawingPV and storage, hybrid inverter
DC-coupled battery with a backup loads panel.
Solar · storageView drawingBattery with partial home backup
Backup gateway and a dedicated backup loads panel.
Solar · storageView drawingSee all solar and battery single line diagrams, or all 40 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.