Template · Solar and storage

Grid-tied PV with DC optimizers single line diagram

An optimizer under each module, two strings to one inverter, backfed at the main panel. Use this for a string inverter with a DC optimizer under each module. The optimizers are drawn between the array and the inverter, because they are part of the rapid shutdown system and they set how the strings are laid out.

A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.

Open this template in the editor Download the SVG

Grid-tied PV with DC optimizers single line diagram: an optimizer under each module, two strings to one inverter, backfed at the main panel.
Grid-tied PV with DC optimizers. 11 devices on an 11 × 17 in sheet with a title block and notes column.

What the reviewer checks on this drawing

The reviewer checks the busbar arithmetic, the inverter output at 125%, the string lengths against the inverter manufacturer’s limits, and that the optimizers and the inverter are listed together for rapid shutdown, with the initiator labelled.

What the drawing shows

Every device on the sheet, in the order power reaches it.

SymbolLabelRating or detailConductors feeding it
Utility sourceUtility service120/240V 1φ 3W
MeterUtility meter200A socketService conductors, per utility
Circuit breaker200A 2PMain breaker
PanelMain panel200A bus · 120/240V
Circuit breakerBranch breakers
To (continues off sheet)To house loads
Circuit breaker40A 2PPV backfeed, opposite end from main
Disconnect switchAC disconnect60A non-fused · outdoors, lockable, visible blade3 #8 Cu + #10 G
InverterString inverter7.6 kW · 240V · 32A, integrated DC disconnect
DC/DC converterDC optimizers20, one under each modulePV wire #10 Cu + #10 G, 2 strings of 10
PV arrayPV array20 × 400W = 8.0 kW DC

Notes on the sheet

  • Busbar check: 200A bus × 120% = 240A ≥ 200A main + 40A PV breaker (NEC 705.12). PV breaker at the opposite end of the bus from the main breaker and labelled.
  • Inverter output 32A × 125% = 40A.
  • Rapid shutdown (NEC 690.12; CEC Rule 64-218): the optimizers and this inverter are to be listed together as a rapid shutdown system. Opening the AC disconnect starts it; that disconnect is outdoors, readily accessible and labelled as the rapid shutdown initiator.
  • String length within the inverter manufacturer’s limits: the fewest and the most optimizers in a string, and the most watts.

Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.

See all solar and battery single line diagrams, or all 80 templates.

Start from this drawing

Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.