Template · Solar and storage

PV through a meter socket adapter single line diagram

A meter collar connects the solar ahead of the main breaker, so the panel bus is left alone. Use this when the panel bus has no room for a backfed breaker and the utility accepts a meter socket adapter. The adapter sits between the meter socket and the meter and connects the solar ahead of the main breaker, so the panel is not opened up.

A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.

Open this template in the editor Download the SVG

PV through a meter socket adapter single line diagram: A meter collar connects the solar ahead of the main breaker, so the panel bus is left alone.
PV through a meter socket adapter. 10 devices on an 11 × 17 in sheet with a title block and notes column.

What the reviewer checks on this drawing

The utility checks that the drawing shows a connection at the meter, not a breaker in the panel, with the adapter’s make, model and rating. The reviewer checks the adapter’s listing and the inverter output at 125% against the adapter’s breaker.

What the drawing shows

Every device on the sheet, in the order power reaches it.

SymbolLabelRating or detailConductors feeding it
Utility sourceUtility service120/240V 1φ 3W
MeterUtility meter200A socketService conductors, per utility
DeviceMeter socket adapter (MSA)200A · between socket and meter, utility approved
Circuit breaker200A 2PMain breaker
PanelboardMain panel200A
Circuit breaker40A 2PAdapter breaker
Disconnect switchAC disconnect60A non-fused, lockable, visible blade3 #8 Cu + #10 G
InverterString inverter7.6 kW · 240V · 32A, integrated DC disconnect
DeviceRapid shutdown (RSD)Module-level devicesPV wire #10 Cu + #10 G, 2 strings
PV arrayPV array20 × 400W = 8.0 kW DC

Notes on the sheet

  • The adapter connects the PV on the supply side of the service disconnect (NEC 705.11 and 230.82(6)). The panel bus is not backfed, so there is no busbar check and no main breaker to change.
  • Adapter listed for the purpose and accepted by the utility for this meter socket. It fits the plug-in socket models its maker lists it for, not a bolt-in socket. Its breaker’s interrupting rating to equal or exceed the available fault current.
  • The disconnect and overcurrent protection for a supply-side connection are to be suitable for use as service equipment (NEC 230.82(6) and 705.11): the adapter’s breaker where its listing says so, otherwise a fused, service-rated AC disconnect.
  • Inverter output 32A × 125% = 40A, the rating of the breaker in the adapter.
  • Give the adapter’s make, model and rating on the interconnection application. The utility pulls and resets the meter, or witnesses it.
  • Rapid shutdown per NEC 690.12 (CEC Rule 64-218).

Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.

See all solar and battery single line diagrams, or all 80 templates.