Ground-mount PV with feeder to the house single line diagram
Array and inverter in the yard, a 250 ft underground feeder and a backfed breaker in the main panel. Use this for an array on a ground mount some distance from the house, with the inverter at the array and an underground AC feeder back to a breaker in the main panel.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks the feeder size against voltage drop, the equipment grounding conductor increased with it, a disconnect at the array and one at the house, the busbar arithmetic, and how the array structure is grounded.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Circuit breaker | 200A 2P | Main breaker | |
| Panel | Main panel | 200A bus · 120/240V | |
| Circuit breaker | Branch breakers | ||
| To (continues off sheet) | To house loads | ||
| Circuit breaker | 40A 2P | PV backfeed, opposite end from main | |
| Disconnect switch | AC disconnect | 60A non-fused, lockable, at the house | 3 #8 Cu + #10 G |
| Disconnect switch | Array disconnect | 60A · NEMA 3R, at the array | 3 #4 Cu + #4 G, underground, 250 ft |
| Grounding electrode | Ground rods | At the array, #6 Cu GEC | |
| Inverter | String inverter | 7.6 kW · 240V · 32A, at the array · DC disconnect | |
| PV array | Ground-mount array | 20 × 400W = 8.0 kW DC | PV wire #10 Cu + #10 G, 2 strings |
Notes on the sheet
- Busbar check: 200A bus × 120% = 240A ≥ 200A main + 40A PV breaker (NEC 705.12). Inverter output 32A × 125% = 40A.
- Feeder increased for voltage drop: 32A over 250 ft on #4 Cu is about 2%. Equipment grounding conductor increased in the same proportion (NEC 250.122(B)): 10,380 cmil × 41,740 ÷ 16,510 = 26,242 cmil, just over the 26,240 of a #6, so #4 Cu.
- A grounding electrode at the array, connected to the equipment grounding conductor at the array disconnect, with the neutral isolated there. Most AHJs treat the array, with its inverter and disconnect, as a structure supplied by a feeder and require it (NEC 250.32); it is good practice in any case. It does not take the place of the equipment grounding conductor run with the feeder.
- The PV circuits stay at the array and enter no building, so rapid shutdown (NEC 690.12) is not called for. Confirm with the AHJ.
- Array wiring within reach guarded or in raceway. Burial depth per the adopted code for the wiring method used.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related solar and battery drawings
Grid-tied PV, string inverter
Load-side connection through a 40A backfed breaker.
Solar · storageView drawingGrid-tied PV, microinverters
Two microinverter branches combined in an AC combiner.
Solar · storageView drawingPV supply-side connection
Line-side tap to a fused, service-rated PV disconnect.
Solar · storageView drawingCommercial rooftop PV, string inverters
DC combiners and two 50 kW inverters into an AC combiner panel, backfed at the switchboard.
Solar · storageView drawingSee all solar and battery single line diagrams, or all 80 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.