Battery with whole-home backup switch single line diagram
Meter-socket backup switch islands the whole panel. Use this where the battery backs up the whole panel through a backup switch mounted at the meter socket.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer looks for utility approval of the switch at the meter socket, the busbar arithmetic on the 225A bus, and the storage output at 125%.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Device | Backup switch (BACKUP SW) | Meter-socket mounted · 200A | |
| Circuit breaker | 200A 2P | Main breaker | |
| Panel | Main panel | 225A bus · 120/240V | |
| Circuit breaker | Existing | All house loads | |
| Load | Existing loads | ||
| Circuit breaker | 60A 2P | ESS | |
| Battery | Battery with integrated inverter | 11.5 kW · 13.5 kWh | 3 #6 Cu + #10 G |
Notes on the sheet
- Busbar check: 225A bus × 120% = 270A ≥ 200A main + 60A ESS breaker. ESS breaker at the opposite end of the bus from the main.
- Backup switch requires utility approval for installation at the meter socket.
- ESS output 48A × 125% = 60A.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related solar and battery drawings
Grid-tied PV, string inverter
Load-side connection through a 40A backfed breaker.
Solar · storageView drawingGrid-tied PV, microinverters
Two microinverter branches combined in an AC combiner.
Solar · storageView drawingPV supply-side connection
Line-side tap with a fused, service-rated PV disconnect.
Solar · storageView drawingPV and storage, hybrid inverter
DC-coupled battery with a backup loads panel.
Solar · storageView drawingSee all solar and battery single line diagrams, or all 40 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.