Template · Solar and storage

Commercial battery storage for peak shaving single line diagram

A 125 kW, 250 kWh battery system backfed at a 480V switchboard, discharging to hold down demand. Use this for a battery system added to a commercial building to cut demand charges. It connects through a breaker at the main switchboard and discharges when the building’s demand nears a setpoint.

A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.

Open this template in the editor Download the SVG

Commercial battery storage for peak shaving single line diagram: A 125 kW, 250 kWh battery system backfed at a 480V switchboard, discharging to hold down demand.
Commercial battery storage for peak shaving. 10 devices on an 11 × 17 in sheet with a title block and notes column.

What the reviewer checks on this drawing

The reviewer checks the output current at 125%, the busbar arithmetic at the switchboard, the disconnect within sight of the system, the system’s listing, and its location and fire protection. The utility checks how export is prevented or limited.

What the drawing shows

Every device on the sheet, in the order power reaches it.

SymbolLabelRating or detailConductors feeding it
Utility sourceUtility service480Y/277V 3φ 4W
Current transformerCT cabinetUtility metering
Circuit breaker600A 3PMain
PanelMain switchboard MSB800A bus · 480Y/277V 3φ 4W
Circuit breakerBranch breakers
To (continues off sheet)To building loads
Circuit breaker200A 3PBESS
Disconnect switchESS disconnect200A · NEMA 3R, lockable, within sight3 #3/0 Cu + #6 G, 2" EMT
DevicePower conversion system (PCS)125 kW · 480V · 150A
BatteryBattery cabinets250 kWh · LFP

Notes on the sheet

  • Power conversion system: 125 kW ÷ (1.732 × 480V) = 150A; × 125% = 188A, protected at 200A on 3/0 Cu (200A at 75 °C).
  • Busbar check at MSB: 600A main + 188A (125% of the system’s output) = 788A, within the 800A rating of the bus, so the BESS breaker may sit anywhere on it (NEC 705.12).
  • The system’s controller reads current transformers at the service and discharges to hold the building’s demand under a setpoint. Export to the utility is blocked or limited as the interconnection agreement requires.
  • Energy storage system listed as a system (UL 9540). Location, spacing, fire detection and signage per NEC Article 706 and the fire code (CEC Section 64).
  • Disconnect lockable and within sight of the system (NEC 706.15). Charging is a load of up to 188A on the 600A main: it is in the service load calculation, or the controller limits it.

Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.

See all solar and battery single line diagrams, or all 80 templates.

Start from this drawing

Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.