Standby generator riser single line diagram
Outdoor service disconnect, automatic transfer switch in the garage and a standby generator in the side yard.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Circuit breaker | 200A 2P | Service disconnect | 3 #2/0 Cu |
| Transfer switch | Automatic transfer switch | 200A · not service rated | 3 #2/0 Cu + #6 G, 2" PVC |
| Circuit breaker | 100A 2P | Generator breaker | |
| Generator | Standby generator | 22 kW · natural gas, 120/240V | 3 #3 Cu + #8 G, 1-1/4" PVC |
| Circuit breaker | 200A 2P | Main breaker | 3 #2/0 Cu + #6 G |
| Panel | Main panel | 200A bus · neutrals isolated | |
| Circuit breaker | Branch breakers | ||
| To (continues off sheet) | To all house loads |
Notes on the sheet
- Service disconnect on the garage exterior wall is the service disconnect and emergency disconnect. Grounding electrode conductor and main bonding jumper terminate there.
- Feeder to the transfer switch and main panel is four-wire: neutrals isolated and the bonding screw removed in the main panel.
- Service and feeder conductors: 3 #2/0 Cu at 175A ≥ 83% × 200A = 166A for a dwelling service.
- Generator 22 kW ÷ 240V = 92A, protected at 100A on #3 Cu (100A at 75 °C).
- Load shedding modules added if the calculated load exceeds the generator rating.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related generator drawings
Portable generator inlet with interlock
Backfed 30A breaker mechanically interlocked with the main.
GeneratorView drawingGenerator with manual transfer switch
Ten-circuit manual transfer switch with an inlet box.
GeneratorView drawingStandby generator, whole-home ATS
Service-rated 200A automatic transfer switch.
GeneratorView drawingStandby generator, essential loads panel
100A transfer switch feeding an essential loads subpanel.
GeneratorView drawingSee all generator single line diagrams, or all 52 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.