Template · Commercial and industrial

Restaurant service with kitchen panel single line diagram

A 400A 120/208V service with a kitchen panel, shunt-trip circuits under the hood and rooftop units. Use this for a restaurant fit-out: a 400A service, a kitchen panel for the cooking equipment, a panel for the dining room and breakers for the rooftop unit and the make-up air unit.

A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.

Open this template in the editor Download the SVG

Restaurant service with kitchen panel single line diagram: A 400A 120/208V service with a kitchen panel, shunt-trip circuits under the hood and rooftop units.
Restaurant service with kitchen panel. 24 devices on an 11 × 17 in sheet with a title block and notes column.

What the reviewer checks on this drawing

The reviewer checks the shunt-trip breakers on the equipment under the hood and what trips them, ground-fault protection in the kitchen, the kitchen feeder’s demand factors, and each HVAC breaker against its nameplate.

What the drawing shows

Every device on the sheet, in the order power reaches it.

SymbolLabelRating or detailConductors feeding it
Utility sourceUtility service120/208V 3φ 4W
Current transformerCT cabinetUtility metering
Circuit breaker400A 3PMain2 sets of 4 #3/0 Cu
PanelMain distribution panel MDP400A · 120/208V 3φ 4W
GroundGrounding electrode#2 Cu GEC
Circuit breaker200A 3PKP
PanelKitchen panel KP225A MLO · 120/208V 3φ 4W4 #3/0 Cu + #6 G
Circuit breaker50A 3PShunt trip
LoadElectric fryer14 kW · 208V 3φ, 39A3 #8 Cu + #10 G
Circuit breaker60A 3PShunt trip
LoadCombi oven15 kW · 208V 3φ, 42A3 #6 Cu + #10 G
Circuit breaker20A 1PGFCI
ReceptacleKitchen receptacles2 #12 Cu + #12 G
Circuit breaker15A 3PEF-1
Disconnect switchDisconnect30A · NEMA 3R3 #12 Cu + #12 G
MotorHood exhaust fan1.5 HP · 208V
Circuit breaker100A 3PLP
PanelboardPanel LP100A · dining room4 #3 Cu + #8 G
Circuit breaker60A 3PRTU-1
Disconnect switchDisconnect60A · NEMA 3R3 #6 Cu + #10 G
LoadRTU-1MCA 44A · MOCP 60A
Circuit breaker40A 3PMAU-1
Disconnect switchDisconnect60A · NEMA 3R3 #8 Cu + #10 G
LoadMake-up air unitMCA 27A · MOCP 40A

Notes on the sheet

  • Cooking equipment under the hood is on shunt-trip breakers. When the hood suppression system discharges it trips them and closes the gas valve (NFPA 96 and the mechanical code). Whether the exhaust fan keeps running and the make-up air stops follows the system listing and the AHJ.
  • Fryer 14 kW ÷ (1.732 × 208V) = 38.9A; × 125% = 48.6A, on a 50A circuit. Combi oven 15 kW = 41.6A; × 125% = 52A, on a 60A circuit. Replace with the nameplate data of the equipment installed.
  • Kitchen panel feeder may use the demand factors for commercial cooking equipment (NEC Table 220.56). They do not apply to the HVAC.
  • Ground-fault protection for kitchen receptacles up to 150V to ground, single-phase to 50A and three-phase to 100A, which takes in cord-connected cooking equipment (NEC 210.8(B)).
  • Service conductors in two parallel sets: 2 × 200A (3/0 Cu) = 400A, on the 400A main. Grounding electrode conductor #2 Cu (NEC Table 250.66).
  • Available fault current marked on the service equipment (NEC 110.24).

Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.

See all commercial and industrial single line diagrams, or all 80 templates.