Irrigation pump service single line diagram
A 480V three-phase service for a 75 HP pump and a centre pivot. Use this for a 480V three-phase service that exists for an irrigation pump: a meter, a small service panel, the pump starter and a circuit for a centre pivot.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The inspector checks the pump conductors and breaker against the motor’s full-load current, the overload setting, the fused, lockable disconnect at the pivot with its grounding electrode, and the grounding electrode at the service.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 480Y/277V 3φ 4W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Circuit breaker | 200A 3P | Main breaker | 4 #3/0 Cu, service entrance |
| Panel | Pump service panel | 200A bus · 480Y/277V 3φ | |
| Grounding electrode | Ground rods | 2 rods, 6 ft apart, #6 Cu GEC | |
| Circuit breaker | 30A 3P | SPD | |
| Surge protective device | SPD | Type 2 | |
| Circuit breaker | 150A 3P | Pump | |
| Motor starter | Pump panel | Disconnect and size 4, starter · NEMA 3R | 3 #1/0 Cu + #6 G |
| Motor | Irrigation pump | 75 HP · 460V · 96A | 3 #1/0 Cu + #6 G |
| Circuit breaker | 20A 3P | Pivot | |
| Fused disconnect | Pivot disconnect | 30A · fused 20A, lockable · at the pivot point | 3 #10 Cu + #10 G, PVC underground |
| Grounding electrode | Ground rod | At the pivot point | |
| Load | Centre pivot | 480V 3φ · 12A |
Notes on the sheet
- Pump motor 75 HP at 460V: 96A (NEC Table 430.250) × 125% = 120A. Conductors 1/0 Cu (150A at 75 °C) to match the 150A breaker, which is within the limit of NEC Table 430.52.
- Pump panel has its own disconnect, within sight of the motor (NEC 430.102), and a starter with an overload relay set from the motor nameplate. Phase-loss protection is worth having on a rural three-phase line.
- The centre pivot is an irrigation machine: a lockable disconnect with overcurrent protection at the point where power connects to it (NEC 675.8), and a grounding electrode at the pivot point for lightning protection (NEC 675.15). Its circuit from the machine’s nameplate.
- Service load: 96A × 125% + 12A = 132A, on the 200A service, with 3/0 Cu service entrance conductors (200A at 75 °C). Some utilities want a disconnect ahead of a 480V self-contained meter: follow the utility’s standard.
- Pivot conductors #10 Cu for voltage drop over the run. Burial depth per the adopted code for the wiring method used.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related commercial and industrial drawings
347/600V service with step-down transformer
Canadian commercial service with a 75 kVA transformer to 120/208V.
CommercialView drawing480Y/277V service with 208V transformer
800A switchboard with a 75 kVA transformer for 120/208V loads.
CommercialView drawingMedium-voltage service with unit substation
13.8 kV breaker with an overcurrent relay, a 1500 kVA transformer and a 2000A 480V switchboard.
CommercialView drawingTenant fit-up panel
New metered 100A feeder and panel from base-building distribution.
CommercialView drawingSee all commercial and industrial single line diagrams, or all 80 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.