Template · EV chargers

DC fast charger with Level 2 chargers single line diagram

One 60 kW fast charger and four Level 2 chargers through a 208V transformer, on a 480V service. Use this for a site with one DC fast charger and a few Level 2 chargers on a new 480V service: the fast charger straight from the switchboard, the Level 2 chargers through a 208V transformer and their own panel.

A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.

Open this template in the editor Download the SVG

DC fast charger with Level 2 chargers single line diagram: one 60 kW fast charger and four Level 2 chargers through a 208V transformer, on a 480V service.
DC fast charger with Level 2 chargers. 24 devices on an 11 × 17 in sheet with a title block and notes column.

What the reviewer checks on this drawing

The reviewer checks the fast charger’s input current from the data sheet at 125%, the transformer’s primary and secondary protection, the secondary bonded as a separately derived system, and the emergency shutoff and disconnect locations.

What the drawing shows

Every device on the sheet, in the order power reaches it.

SymbolLabelRating or detailConductors feeding it
Utility sourceUtility transformer480Y/277V 3φ 4W
Current transformerCT cabinetUtility metering
Circuit breaker400A 3PMain2 sets of 4 #3/0 Cu
PanelSwitchboard SB-1400A · 480Y/277V 3φ 4W
GroundGrounding electrode system#2 Cu GEC
Circuit breaker100A 3PDCFC-1
Disconnect switchDisconnect100A · NEMA 3R, lockable3 #3 Cu + #8 G
EV chargerDC fast charger60 kW · 76A input
Circuit breaker70A 3PT-1 primary
TransformerTransformer T-145 kVA, 480V Δ – 208Y/120V3 #4 Cu + #8 G
Circuit breaker150A 3PSecondary main4 #1/0 Cu + #6 G
PanelEV panel EVP225A bus · 208Y/120V 3φ 4W
GroundT-1 grounding electrode#6 Cu GEC
Circuit breaker40A 2PEV-1
EV chargerEVSE 132A · 6.6 kW2 #8 Cu + #10 G
Circuit breaker40A 2PEV-2
EV chargerEVSE 232A · 6.6 kW2 #8 Cu + #10 G
Circuit breaker40A 2PEV-3
EV chargerEVSE 332A · 6.6 kW2 #8 Cu + #10 G
Circuit breaker40A 2PEV-4
EV chargerEVSE 432A · 6.6 kW2 #8 Cu + #10 G
Circuit breaker100A 3PDCFC-2
Circuit breaker30A 3PSPD
Surge protective deviceSPDType 2

Notes on the sheet

  • Fast charger input current from the manufacturer data sheet; branch circuit at 125% of continuous input: 76A × 125% = 95A, protected at 100A on #3 Cu (100A at 75 °C).
  • T-1: 45 kVA ÷ (1.732 × 480V) = 54A primary; × 125% = 68A, protected at 70A on #4 Cu (85A). Secondary 45 kVA ÷ (1.732 × 208V) = 125A, protected at 150A on 1/0 Cu (150A).
  • Four 32A chargers at 208V: 4 × 6.66 kVA = 26.6 kVA; × 125% = 33.3 kVA, on the 45 kVA transformer.
  • Service conductors in two parallel sets: 2 × 200A (3/0 Cu) = 400A, on the 400A main. The main and the bus leave room for a second fast charger.
  • Transformer T-1 secondary is a separately derived system: system bonding jumper at the EV panel’s main, and a grounding electrode conductor to the building electrode, #6 Cu for 1/0 Cu secondary conductors (NEC 250.30). Service grounding electrode conductor #2 Cu for the two sets of 3/0 Cu (NEC Table 250.66).
  • Emergency shutoff and disconnect locations per the AHJ and charger manufacturer.

Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.

See all EV charger single line diagrams, or all 80 templates.