Template · EV chargers

Commercial Level 2 charger bank single line diagram

Six 32A chargers from a dedicated 208V EV panel. Use this for a workplace, retail or multi-family parking area with a row of Level 2 chargers on a dedicated three-phase EV panel.

A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.

Open this template in the editor Download the SVG

Commercial Level 2 charger bank single line diagram: six 32A chargers from a dedicated 208V EV panel.
Commercial Level 2 charger bank. 20 devices on an 11 × 17 in sheet with a title block and notes column.

What the reviewer checks on this drawing

The reviewer checks each 32A charger on a 40A circuit, the chargers balanced across the three phases, the panel feeder against the total continuous load, and what happens when more chargers are added.

What the drawing shows

Every device on the sheet, in the order power reaches it.

SymbolLabelRating or detailConductors feeding it
Utility sourceUtility service120/208V 3φ 4W
Current transformerCT cabinetUtility metering
Circuit breaker400A 3PMain
PanelMain distribution panel400A · 120/208V 3φ 4W
Circuit breakerExistingBuilding loads
LoadExisting loads
Circuit breaker200A 3PEV feeder
PanelEV panel225A MLO · 120/208V 3φ 4W4 #3/0 Cu + #6 G
Circuit breaker40A 2PEV-1
EV chargerEVSE 132A · 6.6 kW
Circuit breaker40A 2PEV-2
EV chargerEVSE 232A · 6.6 kW
Circuit breaker40A 2PEV-3
EV chargerEVSE 332A · 6.6 kW
Circuit breaker40A 2PEV-4
EV chargerEVSE 432A · 6.6 kW
Circuit breaker40A 2PEV-5
EV chargerEVSE 532A · 6.6 kW
Circuit breaker40A 2PEV-6
EV chargerEVSE 632A · 6.6 kW

Notes on the sheet

  • Chargers balanced across phases A-B, B-C and C-A.
  • Each 32A EVSE is a continuous load on a 40A circuit.
  • Add a networked load management system if future chargers would exceed the 200A feeder.

Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.

See all EV charger single line diagrams, or all 40 templates.

Start from this drawing

Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.