Well pump with constant-pressure drive single line diagram
Submersible pump on a variable frequency drive, with a disconnect within sight.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Circuit breaker | 200A 2P | Main breaker | |
| Panel | Main panel | 200A bus · 120/240V | |
| Circuit breaker | Branch breakers | ||
| To (continues off sheet) | To house loads | ||
| Circuit breaker | 30A 2P | Well pump | |
| Disconnect switch | Disconnect | 30A · NEMA 3R, within sight of drive | 2 #10 Cu + #10 G, 3/4" PVC |
| Variable frequency drive | Pump drive | 2 HP · 18A input, 230V 1φ in · 3φ out | |
| Motor | Submersible pump | 2 HP · 230V 3φ, 8.1A max | 3 #12 Cu + G, submersible pump cable |
Notes on the sheet
- Circuit to the drive sized from its rated input current: 18A × 125% = 22.5A, so #10 Cu on a 30A breaker.
- Drive output current limit set to the motor nameplate maximum (8.1A). Motor overload protection is provided by the drive.
- Pump cable sized for voltage drop over the full length to the pump, per the drive manufacturer table.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related service and panel drawings
Service and main panel upgrade to 200A
New meter socket, service entrance and 200A panel with surge protection.
ServiceView drawingService upgrade with outdoor emergency disconnect
New meter socket and outdoor service disconnect; the panel inside stays and becomes a subpanel.
ServiceView drawingPanel upgrade with grounding system replacement
New panel with rods, water bond, intersystem bonding and surge protection.
ServiceView drawingSubpanel addition
100A four-wire feeder to a new subpanel.
ServiceView drawingSee all service and panel single line diagrams, or all 52 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.