Panel upgrade with grounding system replacement single line diagram
New panel with rods, water bond and intersystem bonding. Use this when a panel change also replaces the grounding: new ground rods, a bond to the water piping and intersystem bonding.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer looks for the main bonding jumper in the main panel only, grounding electrode conductors that are continuous or irreversibly spliced, and a bonding jumper around the water meter.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Circuit breaker | 200A 2P | Main breaker | |
| Panel | New main panel | 200A bus · 120/240V | |
| Ground | Ground rods | 2 rods, 6 ft apart, #6 Cu GEC | |
| Ground | Water pipe electrode | #4 Cu GEC within 5 ft of entry | |
| Ground | Gas pipe bond | By equipment grounding conductor | |
| Device | Intersystem bonding (IBT) | #6 Cu | |
| Circuit breaker | Existing | Branch breakers | |
| Load | Existing loads |
Notes on the sheet
- Main bonding jumper installed in the main panel only.
- Grounding electrode conductors continuous or irreversibly spliced.
- Bonding jumper installed around the water meter and any insulating fittings.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related service and panel drawings
Service and main panel upgrade to 200A
New meter socket, service entrance and 200A panel.
ServiceView drawingSubpanel addition
100A four-wire feeder to a new subpanel.
ServiceView drawingFeeder to detached garage or ADU
Underground feeder, building disconnect and local grounding electrode.
ServiceView drawing400A service with two 200A panels
Class 320 meter socket feeding two main panels.
ServiceView drawingSee all service and panel single line diagrams, or all 40 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.