UPS with battery cabinet and critical panel single line diagram
40 kVA double-conversion UPS feeding a critical loads panel. Use this for a server room or other critical load on a 40 kVA double-conversion UPS with a battery cabinet and a critical loads panel.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks the input breaker at 125% including battery recharge current, a maintenance bypass if the load cannot be dropped for service, and emergency power off and battery room ventilation.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail |
|---|---|---|
| Device | Distribution panel (DP) | 120/208V 3φ 4W |
| Circuit breaker | 150A 3P | UPS input |
| Device | UPS (UPS) | 40 kVA · double conversion |
| Battery | Battery cabinet | 10 min at full load |
| Circuit breaker | 125A 3P | UPS output |
| Panel | Critical loads panel CP-1 | 125A · 120/208V 3φ 4W |
| Circuit breaker | 30A 3P | |
| Load | Rack PDU A | |
| Circuit breaker | 30A 3P | |
| Load | Rack PDU B | |
| Circuit breaker | 20A 1P | |
| Load | Network core |
Notes on the sheet
- 40 kVA at 208V = 111A. Input breaker sized at 125% including battery recharge current.
- Add an external maintenance bypass where the UPS must be serviced without dropping the load.
- Emergency power off and battery room ventilation per the adopted codes.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related commercial and industrial drawings
347/600V service with step-down transformer
Canadian commercial service with a 75 kVA transformer to 120/208V.
CommercialView drawing480Y/277V service with 208V transformer
800A switchboard with a 75 kVA transformer for 120/208V loads.
CommercialView drawingTenant fit-up panel
New metered 100A feeder and panel from base-building distribution.
CommercialView drawingMotor control centre
MCC with starters, a drive, a lighting transformer and a spare bucket.
CommercialView drawingSee all commercial and industrial single line diagrams, or all 40 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.