Temporary construction power single line diagram
100A temporary service on a pole with GFCI circuits. Use this for temporary power on a construction site: a 100A service on a pole, with GFCI-protected circuits for tools and a feed for the site trailer.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer looks for GFCI protection on the receptacle circuits, a pole built to the utility’s standards, the ground rod, and inspection before the service is energized.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail |
|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W, temporary drop |
| Meter | Utility meter | 100A socket on temporary pole |
| Circuit breaker | 100A 2P | Main breaker |
| Panel | Temporary power panel | 100A · NEMA 3R |
| Ground | Ground rod | #6 Cu GEC |
| Circuit breaker | 20A GFCI | |
| Load | Receptacles | GFCI protected |
| Circuit breaker | 20A GFCI | |
| Load | Receptacles | GFCI protected |
| Circuit breaker | 50A 2P | |
| Load | Site trailer | |
| Circuit breaker | 30A 2P | |
| Load | Spider box | GFCI outlets |
Notes on the sheet
- All 125V 15A, 20A and 30A receptacles for construction use are GFCI protected.
- Temporary pole braced and installed to utility standards. Remove at completion.
- Temporary wiring inspected before energizing.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related commercial and industrial drawings
347/600V service with step-down transformer
Canadian commercial service with a 75 kVA transformer to 120/208V.
CommercialView drawing480Y/277V service with 208V transformer
800A switchboard with a 75 kVA transformer for 120/208V loads.
CommercialView drawingTenant fit-up panel
New metered 100A feeder and panel from base-building distribution.
CommercialView drawingMotor control centre
MCC with starters, a drive, a lighting transformer and a spare bucket.
CommercialView drawingSee all commercial and industrial single line diagrams, or all 40 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.