RV pedestal at a house single line diagram
An underground feeder to a pedestal with 50A, 30A and 20A receptacles. Use this for an RV parking pad at a house: an underground feeder to a pedestal with a 50A, a 30A and a 20A receptacle.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The inspector checks the feeder size, ground-fault protection on all three receptacles, the 30A receptacle wired for 120V, the neutral isolated at the pedestal and the burial depth.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Circuit breaker | 200A 2P | Main breaker | |
| Panel | Main panel | 200A bus · 120/240V | |
| Circuit breaker | Branch breakers | ||
| To (continues off sheet) | To house loads | ||
| Circuit breaker | 60A 2P | RV pedestal | |
| Panel | RV pedestal | 100A MLO · NEMA 3R | 3 #6 Cu + #10 G, PVC underground |
| Grounding electrode | Ground rod | At pedestal, where, the AHJ requires it | |
| Circuit breaker | 50A 2P | GFCI | |
| Receptacle | RV receptacle | 50A · NEMA 14-50R, 120/240V | 3 #6 Cu + #10 G |
| Circuit breaker | 30A 1P | GFCI | |
| Receptacle | RV receptacle | 30A · NEMA TT-30R, 120V | 2 #10 Cu + #10 G |
| Circuit breaker | 20A 1P | GFCI | |
| Receptacle | Receptacle | 20A · NEMA 5-20R | 2 #12 Cu + #12 G |
Notes on the sheet
- One RV at a time: the load is that of the largest receptacle, 12,000 VA for the 50A (the method of NEC 551.73(A)). 12,000 VA ÷ 240V = 50A, on the 60A feeder.
- The 30A TT-30R receptacle is 120V only: one pole and a neutral, never wired 240V. The 50A 14-50R is 120/240V, four-wire.
- GFCI protection on all three: outdoor receptacles at a dwelling, 125V through 250V (NEC 210.8(A), 2020 and later). The 2017 edition asked for it on the 20A only. The relief for RV site receptacles in NEC 551.71(F) is for RV parks, not for a house.
- Neutral isolated from the pedestal enclosure and equipment ground bonded. A grounding electrode at the pedestal where the AHJ treats a pedestal fed by a feeder as a separate structure (NEC 250.32).
- Burial depth per the adopted code for the wiring method used.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related service and panel drawings
Service and main panel upgrade to 200A
New meter socket, service entrance and 200A panel with surge protection.
ServiceView drawingService upgrade with outdoor emergency disconnect
New meter socket and outdoor service disconnect; the panel inside stays and becomes a subpanel.
ServiceView drawingPanel upgrade with grounding system replacement
New panel with rods, water bond, intersystem bonding and surge protection.
ServiceView drawingSubpanel addition
100A four-wire feeder to a new subpanel.
ServiceView drawingSee all service and panel single line diagrams, or all 80 templates.