Template · Service and panels

Pool equipment subpanel single line diagram

A 60A feeder to a panel at the equipment pad for the pump, heat pump, lights and a receptacle. Use this for a swimming pool with its own panel at the equipment pad, feeding the pump, a heat pump, the pool lights and a receptacle.

A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.

Open this template in the editor Download the SVG

Pool equipment subpanel single line diagram: A 60A feeder to a panel at the equipment pad for the pump, heat pump, lights and a receptacle.
Pool equipment subpanel. 18 devices on an 11 × 17 in sheet with a title block and notes column.

What the reviewer checks on this drawing

The inspector checks ground-fault protection on the pump, the heat pump, the lights and the receptacle, the equipotential bonding grid, the feeder with an insulated equipment grounding conductor, and where the receptacle is relative to the water.

What the drawing shows

Every device on the sheet, in the order power reaches it.

SymbolLabelRating or detailConductors feeding it
Utility sourceUtility service120/240V 1φ 3W
MeterUtility meter200A socketService conductors, per utility
Circuit breaker200A 2PMain breaker
PanelMain panel200A bus · 120/240V
Circuit breakerBranch breakers
To (continues off sheet)To house loads
Circuit breaker60A 2PPool feeder
PanelPool equipment panel100A MLO · NEMA 3R3 #6 Cu + #10 G, 1" PVC underground
Circuit breaker20A 2PGFCI · pump
MotorPool pump1.5 HP · 230V · 10A, variable speed2 #12 Cu + #12 G
Circuit breaker50A 2PGFCI · heat pump
Disconnect switchDisconnect60A · NEMA 3R, within sight of unit2 #8 Cu + #10 G
DevicePool heat pump (HP)MCA 36A · MOCP 50A
Circuit breaker20A 1PGFCI · lights
DevicePool light transformer (XFMR)300 VA · 120V to 12V, listed for pools2 #12 Cu + #12 G
LightingPool lights12V LED
Circuit breaker20A 1PGFCI
ReceptacleReceptacle6 to 20 ft from pool2 #12 Cu + #12 G

Notes on the sheet

  • Feeder load: heat pump 36A (its minimum circuit ampacity) + pump 10A + lights 2.5A + receptacle 1.5A = 50A, on the 60A feeder.
  • Pump motor: 10A × 125% = 12.5A, on a 20A circuit with ground-fault protection (NEC 680.21(C)).
  • Heat pump breaker does not exceed the nameplate MOCP (50A); conductors sized from the MCA (36A). Replace both with the nameplate data of the installed unit. Ground-fault protection on it as an outdoor outlet at a dwelling (NEC 210.8(F), 2020 and later). The 2023 edition exempted listed HVAC equipment until September 2026, and some local amendments still do.
  • Equipotential bonding under the NEC (680.26): #8 solid copper joining the pool shell steel, the perimeter surface, metal fittings, the pump motor and the heater, and the pool water where nothing bonded is in contact with it. It is a bonding grid and need not be run to the panel.
  • In Canada (CEC Rule 68-058): No. 6 copper, and the pool bonding is connected to the bonding of the panelboard that supplies the pool equipment, which the bonding conductor run with the circuit can do.
  • One receptacle between 6 ft and 20 ft from the pool wall, GFCI protected (NEC 680.22(A)).
  • Pool panel is a subpanel: neutrals isolated, and an insulated copper equipment grounding conductor run with the feeder.

Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.

See all service and panel single line diagrams, or all 80 templates.

Start from this drawing

Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.