Manufactured home service pedestal single line diagram
A 200A meter pedestal beside the home and a four-wire feeder to its panel. Use this for a manufactured or mobile home, where the service equipment stands on a pedestal beside the home and a four-wire feeder runs to the panel inside it.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The inspector checks where the pedestal stands relative to the home, its height above grade, the four insulated feeder conductors, the neutral isolated in the home’s panel, and the grounding electrode at the pedestal.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter-main | Meter pedestal | 200A main breaker, NEMA 3R · service rated | Service lateral, per utility |
| Grounding electrode | Ground rods | 2 rods, 6 ft apart, #6 Cu GEC | |
| Surge protective device | SPD | Type 1 or 2 | |
| Circuit breaker | 200A 2P | Main breaker | 3 #3/0 Cu + #6 G, 2" PVC underground |
| Panel | Home distribution panel | 200A bus · neutrals isolated | |
| Circuit breaker | Branch breakers | ||
| To (continues off sheet) | To home circuits |
Notes on the sheet
- Service equipment is not mounted on the home. The pedestal is within sight of it and not more than 30 ft from its exterior wall, with the bottom of the enclosure at least 2 ft above grade (NEC 550.32).
- Feeder: four insulated conductors, one of them the equipment grounding conductor (NEC 550.33). 3/0 Cu is 200A at 75 °C.
- The neutral is bonded at the pedestal only. In the home’s panel the neutral is isolated and the equipment grounding conductor bonds the enclosure and the chassis.
- The home’s distribution panel is factory installed and is shown for reference.
- Where the AHJ applies NEC 230.85 (2020 and later) to a manufactured home, the pedestal’s main breaker is marked EMERGENCY DISCONNECT, SERVICE DISCONNECT.
- Grounding electrode and a surge protective device, Type 1 or Type 2, at the pedestal (NEC 230.67). Burial depth per the adopted code for the wiring method used.
- In Canada, mobile homes are under CEC Section 70 and CSA Z240.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related service and panel drawings
Service and main panel upgrade to 200A
New meter socket, service entrance and 200A panel with surge protection.
ServiceView drawingService upgrade with outdoor emergency disconnect
New meter socket and outdoor service disconnect; the panel inside stays and becomes a subpanel.
ServiceView drawingPanel upgrade with grounding system replacement
New panel with rods, water bond, intersystem bonding and surge protection.
ServiceView drawingSubpanel addition
100A four-wire feeder to a new subpanel.
ServiceView drawingSee all service and panel single line diagrams, or all 80 templates.