Multi-tenant meter centre single line diagram
Six tenant meters and a house meter on a 400A bus. Use this for a small apartment or commercial building with a meter centre: six tenant meters and a house meter on one 400A bus.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks a multi-family load calculation with demand factors, unit labels that match the suite doors, and the meter centre’s short-circuit rating against the available fault current.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail |
|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W |
| Fused disconnect | Main disconnect | 400A · fused 400A, service rated |
| Panel | Meter centre | 400A bus · 6 tenants and house |
| Meter | Meter 1 | |
| Circuit breaker | 100A 2P | |
| Panelboard | Unit 1 | 100A panel |
| Meter | Meter 2 | |
| Circuit breaker | 100A 2P | |
| Panelboard | Unit 2 | 100A panel |
| Meter | Meter 3 | |
| Circuit breaker | 100A 2P | |
| Panelboard | Unit 3 | 100A panel |
| Meter | Meter 4 | |
| Circuit breaker | 100A 2P | |
| Panelboard | Unit 4 | 100A panel |
| Meter | Meter 5 | |
| Circuit breaker | 100A 2P | |
| Panelboard | Unit 5 | 100A panel |
| Meter | Meter 6 | |
| Circuit breaker | 100A 2P | |
| Panelboard | Unit 6 | 100A panel |
| Meter | House meter | |
| Circuit breaker | 60A 2P | |
| Panelboard | House panel | 60A |
Notes on the sheet
- Service size confirmed by a multi-family load calculation with demand factors.
- Tenant breakers labelled with unit numbers that match the suite doors.
- Meter centre short-circuit rating to equal or exceed the available fault current.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related multi-unit drawings
Duplex with two-gang meter socket
One service drop, two meters, a 100A panel per unit.
Multi-unitView drawingFour-storey apartment panel replacement
Floor panels replaced on existing three-phase risers.
Multi-unitView drawingSee all multi-unit single line diagrams, or all 40 templates.