Rooftop HVAC equipment feeders single line diagram
Mechanical panel with breakers and disconnects sized from nameplate data. Use this for rooftop units and other HVAC equipment fed from a mechanical panel, each with its own breaker and a disconnect at the unit.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks each breaker against the nameplate maximum overcurrent protection (MOCP), each conductor against the minimum circuit ampacity (MCA), a disconnect within sight of every unit, and the service receptacle near the rooftop equipment.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail |
|---|---|---|
| Device | From MDP (MDP) | Existing feeder |
| Circuit breaker | 225A 3P | Main |
| Panel | Mechanical panel MP | 225A · 120/208V 3φ 4W |
| Circuit breaker | 60A 3P | RTU-1 |
| Disconnect switch | Disconnect | 60A · NEMA 3R |
| Load | RTU-1 | MCA 42A · MOCP 60A |
| Circuit breaker | 45A 3P | RTU-2 |
| Disconnect switch | Disconnect | 60A · NEMA 3R |
| Load | RTU-2 | MCA 33A · MOCP 45A |
| Circuit breaker | 30A 2P | CU-1 |
| Disconnect switch | Disconnect | 30A · NEMA 3R |
| Load | CU-1 | MCA 18A · MOCP 30A |
| Circuit breaker | 15A 3P | EF-1 |
| Disconnect switch | Disconnect | 30A |
| Motor | EF-1 | 1 HP exhaust fan |
Notes on the sheet
- Breakers do not exceed the nameplate maximum overcurrent protection (MOCP); conductors sized from minimum circuit ampacity (MCA).
- Disconnect within sight of each unit. Service receptacle within 25 ft of rooftop equipment.
- Replace MCA and MOCP values with the nameplate data of the installed equipment.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related commercial and industrial drawings
347/600V service with step-down transformer
Canadian commercial service with a 75 kVA transformer to 120/208V.
CommercialView drawing480Y/277V service with 208V transformer
800A switchboard with a 75 kVA transformer for 120/208V loads.
CommercialView drawingTenant fit-up panel
New metered 100A feeder and panel from base-building distribution.
CommercialView drawingMotor control centre
MCC with starters, a drive, a lighting transformer and a spare bucket.
CommercialView drawingSee all commercial and industrial single line diagrams, or all 40 templates.
Start from this drawing
Free, in the browser, no account. Start from a template or describe the job in plain words, edit the drawing and export a PDF.