Hot tub with GFCI disconnect single line diagram
A 50A circuit to a spa disconnect within sight of the tub. Use this for an outdoor hot tub on a 240V circuit: a breaker in the main panel, a GFCI spa disconnect within sight of the tub, and flexible conduit to the tub.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The inspector checks the ground-fault protection, the disconnect within sight of the tub and at least 5 ft from the water (in Canada, the GFCI at least 3 m away), the insulated equipment grounding conductor, and the bonding at the tub, which in Canada can mean a bonded ring round it.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 120/240V 1φ 3W | |
| Meter | Utility meter | 200A socket | Service conductors, per utility |
| Circuit breaker | 200A 2P | Main breaker | |
| Panel | Main panel | 200A bus · 120/240V | |
| Circuit breaker | Branch breakers | ||
| To (continues off sheet) | To house loads | ||
| Circuit breaker | 50A 2P | Hot tub | |
| Panel | Spa disconnect | 60A · NEMA 3R | 3 #6 Cu + #10 G, 1" PVC |
| Circuit breaker | 50A 2P | GFCI | |
| Device | Hot tub (SPA) | 240V · 40A nameplate, self-contained, listed | 3 #6 Cu + #10 G, liquidtight flex, 6 ft max |
Notes on the sheet
- Hot tub nameplate 40A: 40A × 125% = 50A circuit on #6 Cu. Replace with the nameplate data of the tub installed.
- Ground-fault protection for the tub (NEC 680.44; CEC Section 68), provided here by the GFCI breaker in the spa disconnect.
- Spa disconnect within sight of the tub and at least 5 ft from its inside wall (NEC 680.13). In Canada the GFCI is kept at least 3 m from the tub (CEC Rule 68-068): put the spa disconnect 3 m or more away.
- Insulated copper equipment grounding conductor run with the circuit conductors, all the way to the tub. Flexible conduit at the tub no longer than 6 ft (NEC 680.42(A)).
- Bonding at the tub per NEC 680.26 as changed by 680.42 for a listed self-contained spa. Follow the installation instructions. In Canada a listed tub is not exempt: CEC Rule 68-058 can ask for bonded reinforcement or a No. 6 copper ring round a permanently installed tub, depending on what it sits on.
- Service load calculation to confirm capacity for the added load.
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related service and panel drawings
Service and main panel upgrade to 200A
New meter socket, service entrance and 200A panel with surge protection.
ServiceView drawingService upgrade with outdoor emergency disconnect
New meter socket and outdoor service disconnect; the panel inside stays and becomes a subpanel.
ServiceView drawingPanel upgrade with grounding system replacement
New panel with rods, water bond, intersystem bonding and surge protection.
ServiceView drawingSubpanel addition
100A four-wire feeder to a new subpanel.
ServiceView drawingSee all service and panel single line diagrams, or all 80 templates.