Fire pump service single line diagram
Tap ahead of the building main to a listed fire pump controller. Use this for an electric fire pump supplied from a tap ahead of the building main, through a listed fire pump controller.
A free template with typical ratings, conductor callouts and general notes. Open it, change what differs on your job, fill in the title block and export a PDF.
Open this template in the editor Download the SVG
What the reviewer checks on this drawing
The reviewer checks the supply arrangement against NEC Article 695 and NFPA 20, or CEC Section 32; overcurrent protection that can carry the motor’s locked-rotor current indefinitely; and a supervised disconnect locked in the closed position.
What the drawing shows
Every device on the sheet, in the order power reaches it.
| Symbol | Label | Rating or detail | Conductors feeding it |
|---|---|---|---|
| Utility source | Utility service | 480Y/277V 3φ | |
| Device | Service tap (TAP) | Ahead of building main | |
| Circuit breaker | 800A 3P | Building main | |
| Panelboard | Main switchboard | Building loads | |
| Fused disconnect | Fire pump disconnect | Service rated, lockable, sized for locked rotor | |
| Device | Fire pump controller (FPC) | Listed · 50 HP | Feeder outside bldg, or 2-hour protected |
| Motor | Fire pump | 50 HP · 460V · 65A FLA |
Notes on the sheet
- Fire pump supply arranged per NEC Article 695 and NFPA 20, or CEC Section 32.
- Overcurrent protection sized to carry the locked-rotor current of the fire pump motor indefinitely.
- Disconnect supervised, locked in the closed position and labelled "Fire pump disconnecting means".
Diagram is schematic and not to scale. Field-verify existing equipment ratings. Ratings and conductor sizes shown are typical. Confirm against the adopted code, the equipment listing and a load calculation before installation. Code references are to the 2023 NEC and the 2024 Canadian Electrical Code: see references and editions.
Related commercial and industrial drawings
347/600V service with step-down transformer
Canadian commercial service with a 75 kVA transformer to 120/208V.
CommercialView drawing480Y/277V service with 208V transformer
800A switchboard with a 75 kVA transformer for 120/208V loads.
CommercialView drawingTenant fit-up panel
New metered 100A feeder and panel from base-building distribution.
CommercialView drawingMotor control centre
MCC with starters, a drive, a lighting transformer and a spare bucket.
CommercialView drawingSee all commercial and industrial single line diagrams, or all 40 templates.